Skip to content
Pump Calculators

Head & Pressure

Friction Loss Calculator

Estimate the head lost to friction in a straight run of pipe carrying water. Enter the flow and the pipe's actual inside diameter, length and absolute roughness.

gpm
ft

Actual inside diameter, not nominal size.

in

From the pipe manufacturer or a reference you trust. Use 0 for hydraulically smooth.

ft

Optional. Blank uses 60 °F. Range 32–200 °F.

°F

How friction loss is calculated

This calculator uses the Darcy-Weisbach equation, hf = f × (L/D) × V²/(2g). The friction factor f is 64/Re for laminar flow (Re < 2300) and the Swamee-Jain equation for turbulent flow (Re ≥ 4000); between those it is an interpolated estimate. Water viscosity comes from Linsley, Kohler & Paulhus (1982), Hydrology for Engineers, Table A-2.

It covers straight pipe only. Fittings, valves and elevation are not included — use the Total Dynamic Head Calculator to combine friction with elevation, pressure and minor losses. Full details are on the methodology page.

Worked example

100 gpm through 200 ft of pipe with a 2.067 in inside diameter and 0.00015 ft roughness, at 60 °F: friction loss ≈ 35.1 ft (≈ 15.2 psi), about 17.6 ft per 100 ft.